products

ThermaFlow TPF Physical Properties

Density:

1.02 - 1.15 g/cm³ depending on inhibitors

pH:

7.5 - 10.5 depending on inhibitors

Boiling Point:

>100°C

Characteristics:

a clear, slightly viscous liquid. It is mildly sweet to the taste and has a non-pungent but characteristic aroma.

Available in:

5, 10, 15, 20, 25, 205 & 1000 litre containers and bulk tankers.

Datasheets

For a quote or assistance

Tel: 01792 586800
email: info@hydratech.co.uk

Non Toxic Heat Transfer Fluid with Antifreeze for use in Hot Water Heating Systems. Based on Propylene Glycol and ASTM D1384 High Temperature Rated Corrosion, Scale & Biological Inhibitors.

ThermaFlow TPF has been especially formulated for use as a Non Toxic heat transfer fluid for use in Hot Water Heating Systems.


Antifreeze AntiFreeze

ThermaFlow TPF is miscible with water in all proportions and can protect Hot Water Heating Systems down to -50°C depending on concentration.

ThermaFlow TPF exhibits super-cooling characteristics and mixtures containing in excess of 50% by volume do not freeze solid, alleviating any concern over possible expansion and burst damage.

non toxic Non Toxic

ThermaFlow TPF has an LD50 toxicity rating (Oral Rat) of ≥15,000 mg/kg of body weight (bw) = “Relatively Harmless”. As confirmed by the Hodge & Sterner Scale.

Corrosion control Corrosion Control

ThermaFlow TPF contains synergistic corrosion inhibitors to protect metals commonly found in such systems. It has been tested in accordance with BS5117 and found to meet BS6580 and ASTM D1384 corrosion standards.

ThermaFlow TPF also contains scale and biological inhibitors to help prevent fouling -thus promoting long operational life and high thermal efficiency.

Biodegradable Biodegradable

ThermaFlow TPF mixtures are readily biodegradable (90% over ten days) and will not remain in the environment or bio-accumulate.

Qulaity Assured Quality Assured

All Hydratech products are manufactured in accordance with certified ISO9001-2008 procedures

Application

As per BSRIA guide BG 29/2012 all pipe-work systems should be clean and free from biological contamination and debris prior to commissioning.

To minimise corrosion air ingress should be minimized. A pressurised system is best.

Determine the total system volume and add ThermaFlow TPF to the system according to the minimum operating temperature required (see table). The minimum dose of ThermaFlow TPF should not be less than 25% of the system volume and the maximum does not normally exceed 60%. We recommend the use of deionised, distilled or UltraPure™ water for this dilution. Avoid water containing high levels of calcium salts or Chlorides [Cl-].

Health & Safety: Please refer to the associated Safety Data Sheet - Available via Login or upon request.

Shelf Life: 3 years when stored in sealed containers out of direct sunlight.

Available in: 5, 10, 15, 20, 25, 205 & 1000 litre containers and bulk tankers.

ThermaFlow TPF can also be supplied as a Ready-To-Use solution.

Mixing Guide

Frost Protection °C v/v of ThermaFlow TPF Refractive Index
-10 25% 1.356
-15 33% 1.364
-20 39% 1.370
-25 44% 1.373
-30 48.5% 1.380
-35 52.5% 1.383

When measuring the percentage of ThermaFlow TPF in the system use a refractometer