Regular analysis can extend the life of both fluid and system. Hydratech’s Fluid Monitoring Program (FMP) is a very straight forward, effective way to proactively monitor closed-loop system condition.
Benefits & Features
- Industrial strength for maximum effectiveness
- Well proven over many years use
- Rapid neutralisation of bacteria & algae
- Rigorous removal slime & biofilms
- Mobilisation of organic sediment & detritus
- Excellent suspension of particulates
- Low foaming, suitable for recirculation
- Hard water tolerant
- Can be disposed of to grey-water drain
- Cost effective and improves heat transfer rate
Purachem HSC1 is a blend of sodium hypochlorite, alkaline builders and sequestrants. The appropriate dose rate and dilution should be determined before use.
Physical Properties
Appearance:Pale yellow liquid
Consistency:Low viscosity
Density:1.05 - 1.2g/cm³
Odour:Chlorine / Beach
Foam:No foam
pH:12.5
Active Biocide:< 3% active Cl.
Available in: 1, 5, 20 litre containers ( bulk containers & tankers available on request )
Dosing
Recommended standard dosing
The standard concentration requires 25 litres per 1000 litres of system volume, or 2.5% v/v of the overall system. At This strength most contaminated systems can be cleaned in a single operation.
We suggest sampling and analysing system fluids biannually to catch any issues early.